DATE 12/15/92 PAGE 1 OF 2 DATA ENTRY ______________________ LEAD ENGINEER__________________ REVIEWER ______________________ DATA ENTRY VERIFIED _____________ APPROVAL ______________________ Q-ACTIVE COMPONENT? [ ] Y [X] N DESIGN ENGINEERING APPROVAL____ (IF YES & NOT DEVELOPED BY DE) =========================================================================== COMPONENT TAG # SUFFIX COMPCODE REF. CALC. 85-EQ-0004-23 R0 2FIS-5610 SWITCH ----------------- --------------- ---------- ------ CAL RANGE: LOWER 0 UPPER 3500 UNITS GPM ------ ------ ---- CAL INPUT: LOWER 4 UPPER 20 UNITS MADC ------ ------ ---- CAL OUTPUT:LOWER NA UPPER NA UNITS ZZZ ------ ------ ---- CHG SOURCE DOC# 92-R-2009-26 ------------------------- =========================================================================== SET ENG PROC ENG COMP/TOLERANCE ENG ACD FUNCTION DESCRIPTION POINT UNIT SETPT UNIT OVER UNDER ACT A 2P35A DISCHARGE FLOW LOW 13.143 MADC 2000.0 GPM 13.303 12.983 CLOSF - ------------------------- ------ ---- ------ ---- ------ ------ ----- SP SEQ RESET VALUE/LIMIT FIXED /NA NOTE ALARM 2K06-E1 ----- ------ ------ ------------------------- =========================================================================== SET ENG PROC ENG COMP/TOLERANCE ENG ACD FUNCTION DESCRIPTION POINT UNIT SETPT UNIT OVER UNDER ACT A 2P35A DISCHARGE FLOW HIGH 5.60 MADC 350.0 GPM 5.76 5.44 CLOSR - ------------------------- ------ ---- ------ ---- ------ ------ ----- SP SEQ RESET VALUE/LIMIT FIXED /NA NOTE ALARM 2K06-D1 ----- ------ ------ ------------------------- =========================================================================== SET ENG PROC ENG COMP/TOLERANCE ENG ACD FUNCTION DESCRIPTION POINT UNIT SETPT UNIT OVER UNDER ACT - ------------------------- ------ ---- ------ ---- ------ ------ ----- SP SEQ RESET VALUE/LIMIT / NOTE ----- ------ ------ ------------------------- =========================================================================== SET ENG PROC ENG COMP/TOLERANCE ENG ACD FUNCTION DESCRIPTION POINT UNIT SETPT UNIT OVER UNDER ACT - ------------------------- ------ ---- ------ ---- ------ ------ ----- SP SEQ RESET VALUE/LIMIT / NOTE ----- ------ ------ ------------------------- =========================================================================== DATE 12/15/92 PAGE 2 OF 2 DATA ENTRY ______________________ LEAD ENGINEER__________________ REVIEWER ______________________ DATA ENTRY VERIFIED _____________ APPROVAL ______________________ Q-ACTIVE COMPONENT? [ ] Y [X] N DESIGN ENGINEERING APPROVAL____ (IF YES & NOT DEVELOPED BY DE) =========================================================================== COMPONENT TAG # SUFFIX COMPCODE REF. CALC. 85-EQ-0004-23 R0 2FIS-5616 SWITCH ----------------- --------------- ---------- ------ CAL RANGE: LOWER 0 UPPER 3500 UNITS GPM ------ ------ ---- CAL INPUT: LOWER 4 UPPER 20 UNITS MADC ------ ------ ---- CAL OUTPUT:LOWER NA UPPER NA UNITS ZZZ ------ ------ ---- CHG SOURCE DOC# 92-R-2009-26 ------------------------- =========================================================================== SET ENG PROC ENG COMP/TOLERANCE ENG ACD FUNCTION DESCRIPTION POINT UNIT SETPT UNIT OVER UNDER ACT A 2P35B DISCHARGE FLOW LOW 13.143 MADC 2000.0 GPM 13.303 12.983 CLOSF - ------------------------- ------ ---- ------ ---- ------ ------ ----- SP SEQ RESET VALUE/LIMIT FIXED /NA NOTE ALARM 2K05-E1 ----- ------ ------ ------------------------- =========================================================================== SET ENG PROC ENG COMP/TOLERANCE ENG ACD FUNCTION DESCRIPTION POINT UNIT SETPT UNIT OVER UNDER ACT A 2P35B DISCHARGE FLOW HIGH 5.60 MADC 350.0 GPM 5.76 5.44 CLOSR - ------------------------- ------ ---- ------ ---- ------ ------ ----- SP SEQ RESET VALUE/LIMIT FIXED /NA NOTE ALARM 2K05-D1 ----- ------ ------ ------------------------- =========================================================================== SET ENG PROC ENG COMP/TOLERANCE ENG ACD FUNCTION DESCRIPTION POINT UNIT SETPT UNIT OVER UNDER ACT - ------------------------- ------ ---- ------ ---- ------ ------ ----- SP SEQ RESET VALUE/LIMIT / NOTE ----- ------ ------ ------------------------- =========================================================================== SET ENG PROC ENG COMP/TOLERANCE ENG ACD FUNCTION DESCRIPTION POINT UNIT SETPT UNIT OVER UNDER ACT - ------------------------- ------ ---- ------ ---- ------ ------ ----- SP SEQ RESET VALUE/LIMIT / NOTE ----- ------ ------ ------------------------- ===========================================================================